All cooling towers operate on the principle of removing heat from water by evaporating a small portion of the water that is recirculated through the unit. The heat that is removed is called the latent heat of vaporization. Each one pound of water that is evaporated removes approximately 1,000 BTU's in the form of latent heat.
COOLING TOWER TERMS AND DEFINITIONS
BTU (British Thermal Unit)
A BTU is the heat energy required to raise the temperature of one pound of water one degree Fahrenheit in the range from 32° F to 212° F
Cooling Range
The difference in temperature between the hot water entering the tower and the cold water leaving the tower is the cooling range.
Approach
The difference between the temperature of the cold water leaving the tower and the wet- bulb temperature of the air is known as the approach. Establishment of the approach fixes the operating temperature of the tower and is a most important parameter in determining both tower size and cost.
Drift
The water entrained in the air flow and discharged to the atmosphere. Drift loss does not include water lost by evaporation. Proper tower design can minimize drift loss.
Heat Load
The amount of heat to be removed from the circulating water within the tower. Heat load is equal to water circulation rate (gpm) times the cooling range times 500 and is expressed in BTU/hr. Heat load is also an important parameter in determining tower size and cost.
Ton
An evaporative cooling ton is 15,000 BTU's per hour.
Wet-Bulb Temperature
The lowest temperature that water theoretically can reach by evaporation. Wet-Bulb temperature is an extremely important parameter in tower selection and design and should be measured by a psychrometer
Pumping Head
The pressure required to pump the water from the tower basin, through the entire system and return to the top of the tower.
Makeup
The amount of water required to replace normal losses caused by bleed off, drift, and evaporation.
Bleed Off
The circulating water in the tower which is discharged to waste to help keep the dissolved solids concentration of the water below a maximum allowable limit. As a result of evaporation, dissolved solids concentration will continually increase unless reduced by bleed off.
This is where all refrigeration guru are welcome. Chilled Water Temperature Range: Increasing the chilled water temperature range reduces the required flow rate and consequently the pump and piping sizes.
Popular Posts
-
All cooling towers operate on the principle of removing heat from water by evaporating a small portion of the water that is recirculated thr...
-
The cooling tower is the operational portal to the natural evaporative "heat sink" for a commercial or industrial cooling system. ...
-
What is low delta T syndrome? Common problem with primary- secondary systems Definition- when the design load delta T is not maintained; Wor...
-
Welcome to all Hamwalk district great people. We continued to strive for excellence because we know the happiness of our life depends on the...
-
http://my.facilitiesnet.com/blogs/MainFeed.aspx
-
Air conditioning automatic control system An air conditioning automatic control system or simply a control system, primarily modulates...
-
The most important things expected from facilities managers today is to understand what your organization's overall strategic goal is an...
-
Increasing the condenser water temperature range reduces the condenser water flow, which requires smaller pumps and piping. It also increase...
-
FERNGULLYBAMBO: myfacilitiesnet
Sunday, July 19, 2009
Sunday, July 5, 2009
HAMWALK DISTRICT ONE LOVE REUNION
Subscribe to:
Posts (Atom)